天水二一三DZX2-32NL系列漏电断路器选型手册

绝世美人儿
754次浏览
2020年07月30日 08:02
最佳经验
本文由作者推荐

江西省财政厅网-个人学期总结


DZX2-32NL系列漏电断路器
DZX2-32NL系列漏电断路器
DZX 2-32NL Range Leakage Circuit Breakers
一、用途 APP LICATION
  DZX2-32NL系列漏电断路器适用于交流50Hz,额定电压220V,额 定电流
32A及以下的电路中,提供高水平的对地泄漏电流保护。同时,可提供过载和短
路保护 。对下列情况提供保护:
  DZX2-32NL range residual current circuit-breaker are suitable for
using in circuit of AC 50Hz, rated voltage is 220V, rated current up to 32A
and below to supply the high-level residual current protection, over-load
and short-circuit protection. To supply the protections for the following
situations:
△ 对间接触电提供保护。
Leakage protection against personnel indirect electroshock.

对直接触电提供保护。
Leakage protection against personnel direct electroshock.
△ 对因电器设备的绝缘故障引起的对地泄露电流提供保护。
Leakage protection against equipment insulation failure.
二、结构特点 STRUCTURE FEATUR

产品体积小,重量轻,分断能力高,宽度仅36mm ,具有高水平的对地泄漏电流
保护组件,同时具有一个保护极和一个可开闭中性极。
The breakers have the following characteristics: compact size, light weight,
high breaking capacity,wide only 36mm ,it have a high-level residual current
protection part and a protection pole and a open-close neutrality pole.

产品符合IEC61009,GB16917等标准。
The products comply with the demands of the following standards:
IEC61009、GB16917.
三、型号及其含义 TYPE AND MEANS
DZX2
32
NL
额定电流
Rated current
特征代号:具有漏电保护
Features of the code:With leakage protection
特征代号:具有可开闭中性极
Features of the code:
Can be neutral with a very open- close
壳架等级额定电流

Rated current level of aircraft shell
设计序号
Design serial number
小容量
Small capacity
低压断路器
Low- voltage circuit breakers
四、工作条件及安装条件
WORKING AND INSTALLATION CONDITION
△ 环境温度:-5℃~+40℃,且24h内的平均温度不超过+35℃;
Environment temperature : -5℃~+40℃, the average hours of temperature
exceeding +35℃ during 24 hours.

海拔高度:不超过2000m; levation: ≤2000m


环境条件 Environment condition:
△ 应无引起爆炸危险的介质,也无腐蚀和破坏绝缘的有害气体和导电尘埃;
There must be not any explosive medium and there must be not any gas


which would corrode metal or any conducting dust which would destroy the
insulation.
△ 安装场所的外磁场,任何方向均不应超过地磁场的5倍;
The location of the installation of any external magnetic field in the direction
of the geomagnetic field should not exceed 5 time

应安装和使用在无明显冲击和振动的地方;
Products should be used in no significant impact and vibration place.
△ 安装类别:III; Installing categories: Class Ⅲ
△ 安装条件:采用35mm标准卡轨安装,安装面与垂直面的倾斜度不大于5°。
Installing condition: mounted by 35mm standard rail track. The tilt gradient
between installation face and vertical face should ≤5°
五、主要技术参数 MAIN TECHNICAL PARAMETERS
■ 基本参数 Basic technical parameters
壳架等级
额定漏电额定电压(V)
额定电
额定漏电动额定漏电不
额定电
分断时间t
分断能力
Rated


流(A)
流(A)
作电流(mA )动作电流(mA)
Rated
(A)
operating
FrameRated
RatedRated
Operating
residualresidual residual
Breaking
voltage
pole
rated
current
current
workingnon- workingbreaking
capacity
current current t ime
220
1P+N
32
6,10,16,
20,25,323015
t
≤0.1s
4500

过电流脱扣特性表 Over-current instantaneous action
试验电流(A)
额定 电规定起始
Testing
流(A)时间
预期结构
基准温度
cur rent
RatedOrder
Expectancy
状态
Benchmar k
备 注
current time
ending
Initial < br>state
temperature
remark
所有电流
冷态
1.13ln
规格
t≤1h
All current
不脱扣
Cold
state
所有电流
冷态
电流在5S内平稳地
1.45ln
规格
t<1h
脱扣
Cold
All current
state
Current
上升至1.45 ln
steady up to
provide math in 5s
所有电流
冷态
2.55ln
规格All
1s<t<60s
脱扣
Cold
current
state
30℃
所有电流
冷态
5ln
规格
0.1s内
不脱扣
Cold
闭合辅助开关
All current
state
接通电流
Closed auxiliary
所有电流
冷态
switch connected
10ln
规格
0.1s内
脱扣
Cold
to current
All current
state
注:DZX2-32NL漏电断路器内的滤波装置,能防止瞬间电压(照明及其它设备
的线路干扰)和瞬间电流(如较大的容性负载线路)引起的误动作。
Note: Leakage circuit breakers inside the filtering device, to prevent the
instantaneous voltage (lighting and other equipment interfere with the line)
and the current moment (such as large capacitive load line) caused by
malfunction.
■ 动作特性曲线 Action feature cur ves
DZX2-32NL系列漏电断路器


DZX2-32NL系列漏电断路器
t(s)
C型:(5~10)In
10000
5000
1h
2000
1000
500
200.
100
50
20
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.01
0.001
0.002
0.001
0.5
1
2
3
4
5
710
20
30
50
70
100
200
IIn

特殊规格漏电断路器
Special character residual current circuit- breaker
△ 用户可根据需要特殊订制带分励脱扣功能的漏电断路器DZX2-32NLFL和 带过
电压保护功能的漏电断路器DZX2-32NLGY。
Users can be special ordered with separation at the release function DZX2-
32NLFL leakage circuit breakers and over-voltage protection with the
leakage circuit breakers DZX2-32NLGY.

DZX2-32NLF L除具有过载、短路保护、漏电保护功能外,还具有分励脱扣功
能,其接线图如下:
DZX2-32NLFL addition to overload, short circuit protection, leakage protection,
but also has separation function. The products wiring picture as follow:

注(Note):

图中虚线所示需由用户外接,以实现分
励脱扣功能;
The picture shown in dotted line by
external users in order to achieve
separation function.

用户无需给分励脱扣器外接电源。
Users need not to release an external
power supply for separation.
△ DZX2-32NLGY除具有过载、短路、漏电保护功能外,还具有过电压保护功能。
当电源电压上升 到280V±5%时,断路器脱扣,实现线路的过电压保护功能。
DZX2-32NLGY addition to overload, short circuit, leakage protection, but
also with over-voltage protection. When the power supply voltage up to
280V ±5%.


△ DZX2-32NLGY断路器与普通的DZX2- 32NL外部接线完全相同。
DZX2-32NLGY circuit breaker with the common external wiring DZX2-
32NL exactly the same.
六、外形及安装尺寸
OUTLINE DIMENSIONS AND MOUNTING DIMENSIONS
七、使用说明 OPERATING INSTRUCTION

漏电断路器结构决定了相线和N线不能接反,必须按端子标识接线。
Leakage circuit breakers in line with the structure of the decision and can not
take anti-N line; the logo must be terminal connection


接线采用带夹头的接线端子,使用10mm
2
及以下的导线。
Chuck connection with the use of the terminals, the use of 10mm
2
and
below the wire

接线端子必须紧固。 Terminal Blocks must fasten
.


应用指南:Application Guide:

每月按压一次试验按钮,检查漏电保护装置的动作。
Push a button to test each month to check leakage protection device action

当漏电保护装置动作时,装置的正面有红色的机械指示。
When the action leakage protection device, the device has a red front of the
machine instructions

当重新闭合断路器时,保护装置自动复位。
When the circuit breaker to close, the protection device automatically reset.

断路器不能对相线与N线之间的触电进行保护。
Circuit breaker can not be compared to the N line with the line between the
electric shock protection.
八、订货须知 ORDER REMARK
■ 用户订货必须明确断路器名称、型号、规格及数量。
Users need attention the entitle type, character and volume of breaker.
例如:DZX2-32NL 16A 漏电断路器 8台
Example: DZX2-32NL 16A Leakage Circuit Breakers 8 sets
■ 特殊订制产品需写明型号DZX2-32NLFL或DZX2-32NLGY。
Specially customize products need attention the type: DZX2-32NLFL or
DZX2-32NLGY.